Multi Core Flexible Power Cord

Conductor : Plain Annealed Copper Wire
Insulation : PVC     V75     ( 75°C )
Sheath : PVC / NBR     V75
Voltage : 250 / 440   V
Standard Applicable : AS3191    (BS6500)
Typical Features :  
Code
No
Size
sq mm
Conductor
Dia / mm
Ins Thick
mm
Sheath Thick
mm
Nom O / D
mm
Current Rating
( Amps ) #
Approx Weight
km / kg
3 Phase Voltage Drop
( mV / A / M )
Max DC Resistance
( Ohm / km )
C2010
2 X 1.0
0.20
0.6
0.8
  7.0
10
  70
    43.0 *
18.10
C2015
2 X 1.5
0.25
0.7
0.8
  7.9
15
  90
    31.0 *
12.10
C3010
3 X 1.0
0.20
0.6
0.8
  7.4
10
  90
37.0
18.10
C3015
3 X 1.5
0.25
0.7
0.9
  8.6
15
120
26.0
12.10
C3025
3 X 2.5
0.25
0.8
1.1
10.6
20
180
16.0
  7.41
C3040
3 X 4.0
0.30
0.8
1.1
11.7
25
235
  9.6
  4.70
C4010
4 X 1.0
0.20
0.6
0.9
  8.3
10
100
37.0
18.10
C4015
4 X 1.5
0.25
0.7
1.0
  9.5
15
145
26.0
12.10
C4025
4 X 2.5
0.25
0.8
1.1
11.5
20
210
16.0
  7.40
C4040
4 X 4.0
0.30
0.8
1.1
12.7
25
290
  9.6
  4.70
C5010
5 X 1.0
0.20
0.6
0.9
  9.0
10
120
37.0
18.10
C5015
5 X 1.5
0.25
0.7
1.1
10.5
15
170
26.0
12.10
C5025
5 X 2.5
0.25
0.8
1.2
12.5
20
260
16.0
  7.41
C5040
5 X 4.0
0.30
0.8
1.8
15.6
25
400
  9.6
  4.70
 
 # Protected from direct sun light .
 
 * Single phase voltage drop .  DC resistance measured at 20 oC ambient temperature .